eFlow6NB Power Supply/Charger
-
Input
- Voltage: 120VAC, 60Hz, 3.5A max.
- Input Fuse: 5A / 250V.
-
Output
- Voltage: 24VDC.
- Current: 6A continuous.
- Other: Overvoltage protection. Filtered and regulated.
-
-
Battery Backup (not included)
- Capacity: 7AH / 12VDC (Up to 2 within enclosure). 40 AH / 65 AH (requires separate enclosure).
- Type: Sealed lead acid or gel type.
- Fuse Rating: 10A/32V.
- Failover: Upon AC loss, instantaneous.
-
Supervision
- AC Failure: Form C contacts.
- Battery: Form C contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units. Prevents deep battery discharge.
-
Indicators LED
- Input: 120VAC is present.
- DC Output: Powered.
- Battery: Discharged or not connected.
-
PDS8 Dual Input Power Distribution Module
-
Input
- Voltage: 12VDC from VR6 and 24VDC from eFlow6NB.
- Input Fuse: 10A / 250V.
-
Outputs
- Voltage: 12VDC and/or 24VDC.
- Any of the eight (8) power outputs are selectable to follow power Input 1 or Input 2.
- Individual outputs may be set to OFF position for servicing.
-
Outputs Ratings
- Fuses: 3A / 32V.
-
Indicators LED
- DC Output Eight (8) individual output LEDs.
- Green: 12VDC
- Red: 24VDC.
-
-
VR6 Voltage Regulator
-
Input
- Voltage: 24VDC from eFlow6NB.
-
Output
- Voltage: 12VDC.
- Current: 6A continuous.
- Other: Surge suppression.
-
Indicators LED
- Input: 24VDC is present.
- Output Powered.
-
-
ACM4 Access Power Controller
-
Input
- Voltage: 24VDC from eFlow6NB.
- Input Fuse: 10A / 32V.
-
Outputs
- Voltage: 24VDC.
- Four (4) independently controlled 2.5A outputs:
- a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
- b) Four (4) dry form C 5A rated relay outputs.
- c) Any combination of the above.
- Four (4) auxiliary power outputs (unswitched).
-
Outputs Ratings
- Fuses: 3A / 32V.
-
Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized).
- Green LED: FACP disconnect is triggered.
-