Description
Altronix T2MK7F4D 4-Door Altronix/Mercury Access and Power Integration Kit
Part Number: T2MK7F4D |
Manufacturer: Altronix |
Description
Buy The Altronix T2MK7F4D From ACR Security at a Discounted Price, In Stock, Ships Today
4-Door Altronix/Mercury Access and Power Integration Kit - Trove2M2 with eFlow104NB, ACM4CB, PD8ULCB, RSB1
-
eFlow104NB Power Supply/Charger
-
Input
- Voltage: 120VAC, 60Hz. 4.5A max.
- Input Fuse: 6.3A / 250V.
-
Outputs
- Voltage: 24VDC @ 10A.
- Auxiliary: 1A (unswitched).
- Protection: Overvoltage protection. Filtered and regulated.
-
-
Battery Backup (not included)
- Type: Sealed lead acid or gel type.
- Fuse Rating: 10A/32VDC.
- Failover: Upon AC loss, instantaneous.
-
Fire Alarm Disconnect
- Supervised: Latching or non-latching.
- EOL: 10K Resistor.
-
Supervision
- AC Failure: Form C contacts.
- Battery: Form C contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units. (depending on the power supply). Prevents deep battery discharge.
-
Indicators LED
- AC Input: 120VAC is present.
- DC Output: Powered.
- Battery: Discharged or not connected.
-
ACM4CB Access Power Controller
-
Input
- Voltage: 24VDC from eFlow6NB.
- Main Fuse: 10A / 32V.
-
Outputs
- Voltage: 24VDC.
- Four (4) independently controlled 2.5A outputs:
- a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
- b) Any combination of the above.
- Four (4) auxiliary power outputs (unswitched).
-
Outputs Ratings
- PTCs: 2.5A.
-
Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized).
- Green LED: FACP disconnect is triggered.
-
-
PD8ULCB Dual Input Power Distribution Module
-
Input
- Voltage: 24VDC from eFlow104NB.
-
Outputs
- Class 2 power-limited auto-resettable outputs.
- Voltage: 24VDC.
- PTCs: 2.5A.
-
Indicators (LED)
-