Description
Altronix TANGO8ACB Access Power Controller with PoE Driven Power Supply/Charger, BC400 Enclosure
Part Number: TANGO8ACB |
Manufacturer: Altronix |
Description
Buy The Altronix TANGO8ACB From ACR Security at a Discounted Price, In Stock, Ships Today
Access Power Controller with PoE Driven Power Supply/Charger, BC400 Enclosure
-
Ethernet Input
- 802.3bt PoE up to 90W (or 802.3at up to 30W or 802.3af up to 15W)
-
Power Output (when using 802.3bt 90W)
- 12VDC up to 5.4A (65W) and/or 24VDC up to 2.7A (65W).
- Combined output not to exceed 65W.
-
When charging batteries:
- 12VDC up to 4.6A (55W) and/or 24VDC up to 2.3A (55W)
- Combined output not to exceed 55W.
-
Ethernet Output
- Pass-through Ethernet Port (data only).
-
Battery Charging Circuit
- 12VDC battery charger for Lithium Iron Phosphate Battery (LiFePO4 only).
- Unique technology allows for single battery to backup 12VDC and/or 24VDC systems
-
Supervision
- Loss of PoE Input.
- Battery Supervision.
-
Indicators (LED)
- Input: Indicates input voltage is present.
- Output: Indicates normal operating condition.
- PoE Type: PoE Class Indicator
- Supervision: PoE Fail or BAT Fail.
-
ACMS8/ACMS8CB Access Power Controller:
-
Inputs
- 12VDC and 24VDC from Tango1B, factory wired.
- Current Consumption: 0.6A @ 12V, 0.3A @ 24V with all relays energized
- Main Fuse Rating 15/32A.
-
Trigger Inputs
- Eight (8) individually controlled trigger inputs:
- a) Normally open (NO) inputs.
- b) Normally closed (NC) inputs.
- c) Open collector sink inputs.
- d) Wet Input (5VDC - 24VDC) with 10K resistor.
- e) Any combination of the above.
-
Outputs
- Eight (8) PTC protected outputs rated @ 2A per output, Class 2 power-limited. Total output 16A max.
- Do not exceed the individual power supply ratings.
- Eight (8) selectable 12VDC or 24VDC independently controlled outputs or eight (8) indepently controlled Form C relay outputs:
- a) Fail-Safe and/or Fail-Secure power outputs.
- b) Form C Relays. 28VAC or VDC @ 2.5A Rated.
- c) Auxiliary power outputs (unswitched).
- d) Any combination of the above.
- Any of the eight (8) power outputs are selectable for 12VDC or 24VDC.
- Individual outputs may be set to OFF position for servicing.
-
-
Output Ratings
- Fuses are rated 2.5A each, PTCs are rated at 2A.
-
Fire Alarm Disconnect
- Supervised: Latching or non-latching, individually selectable for any or all of the eight (8) outputs.
- EOL: 10K Resistor.
-
Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized).
- Blue LED FACP disconnect is triggered.
-
Individual voltage LEDs
- Green: 12VDC
- Red: 24VDC.