Altronix MAXFIT7F16APS EFLOW104NB/VR6/2-ACMS8/PD16W

filler

Price:
Sale price$819.21

Description

Altronix MAXFIT7F16APS EFLOW104NB/VR6/2-ACMS8/PD16W

Part Number: MAXFIT7F16APS
Manufacturer: Altronix

Description
Buy The Altronix MAXFIT7F16APS From ACR Security at a Discounted Price, In Stock, Ships Today

Altronix MAXFIT7F16APS EFLOW104NB/VR6/2-ACMS8/PD16W

eFlow104NB Power Supply/Charger
Input
Voltage: 120VAC, 60Hz, 4.5A max.
Main Fuse: 6.5A / 250V.
Outputs
Voltage: 24VDC @ 10A.
Auxiliary: 1A (unswitched).
Protection: Overvoltage protection. Filtered and regulated.
Back-up Battery (not included)
Type: Sealed lead acid or gel type.
Fuse Rating: 10A/32VDC.
Failover: Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised: Latching or non-latching.
EOL: 10K Resistor.
Supervision
AC Failure: Form C contacts.
Battery: Form C contacts.
Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Indicators (LED)
AC Input: 120VAC is present.
DC Output: Powered.
Battery: Discharged or not connected.
PD16W Power Distribution Module
Input
Voltage: 24VDC from eFlow104NB.
Outputs
Voltage: 24VDC.
Sixteen (16) fuse protected outputs.
3.5A per output max.
Output Fuses: 3.5A/250V.
Indicators (LED)
Green LED: DC Output.
VR6 Voltage Regulator
Input/Output
Voltage Range: 24VDC @ 10A = Output: 12VDC @ 6A.
Output
12VDC regulated output.
Output rating 6A max.
Surge suppression.
Indicators (LED)
Input: Indicates input voltage is present.
Output: Indicates normal operating condition.
Two (2) ACMS8 Dual Input Access Power Controllers
Input
Two (2) independent low voltage inputs.
Input Fuse: 15A/32V.
Trigger Inputs:
Eight (8) individually controlled trigger inputs:
a) Normally open (NO) inputs.
b) Normally closed (NC) inputs.
c) Open collector sink inputs.
d) Wet Input (5VDC - 24VDC) with 10K resistor.
e) Any combination of the above.
Outputs
Fuse protected outputs rated @ 2.5A per output, non power-limited. Total output 20A max.
Eight (8) selectable 12VDC - 24VDC independently controlled outputs or eight (8) indepently controlled Form C relay outputs:
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form C Relays. 28VAC or VDC @ 2.5A Rated.
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Any of the eight (8) fuse protected power outputs are selectable to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Output Fuses
3A/32V each.
Total output current is determined by the power supply, not to exceed a maximum of 10A for each input.
Fire Alarm Disconnect
Supervised: Latching or non-latching, individually selectable for any or all of the eight (8) outputs.
EOL: 10K Resistor.
Indicators (LED)
Red LEDs: Outputs are triggered (relays energized).
Blue LED: FACP disconnect is triggered.
Individual voltage LEDs:
Green: 12VDC
Red: 24VDC.
Environmental
Temperature
Operating: 0ð C to 50ð C (32ð F to 122ð F).
Storage: - 20ð C to 70ð C ( - 4ð F to 158ð F).
Relative Humidity
Relative Humidity 85% +/- 5%.
BTU/Hr (approx.):
177 BTU/Hr.

Recently Viewed Products